Short-circuit protection | When a short circuit occurs, the intelligent circuit breaker will be immediately disconnected to ensure the safety of power consumption, and the breaking capacity is 10kA. |
Overvoltage protection | When the voltage exceeds the overvoltage set value, the intelligent circuit breaker will automatically open; When the voltage returns to normal, the intelligent circuit breaker will automatically close in about 20s. |
Undervoltage protection | When the voltage is lower than the undervoltage set value, the intelligent circuit breaker will automatically open; When the voltage returns to normal, the intelligent circuit breaker will automatically close in about 20s. |
Over-temperature protection | When the temperature communication line contact temperature exceeds 75°C, the device will push alarm information. Above 80°C for 15s, the switch module will be automatically disconnected. |
Overload protection | When the line current is greater than the rated current, the device will push an early warning message. When the current current is greater than 1.5 times the rated current, the switching module is automatically disconnected. |
Leakage protection | When the circuit breaker detects that the residual current value reaches 30mA, the protection is automatically disconnected immediately. |
Phase loss protection | When a three-phase product is out of phase, the phase loss protection is triggered and the protection is immediately disconnected. |
Local latch | After the local lock is pulled out, it cannot be closed locally or remotely, ensuring the safety of personnel during maintenance. |
Local fault light | Any abnormal operating parameters such as voltage, current, leakage, temperature, etc. can be judged by the local fault lamp, which can effectively troubleshoot the fault. |
Remote control | Remote switch operation through mobile app and web management platform. |
Timing control | Set one or more timing to the line to realize automatic switch control. |
Energy metering | The circuit breaker module can measure the power consumption of the line, and the current and historical power consumption of each line can be viewed through the mobile app and web management platform. |
Share the device | The same device can be shared with others for common use (up to 5 shares on the same device), and administrators can assign permissions to the people who share it. |
Operational logs | Records the actions of all users corresponding to the device. Including: switching lines, executing scenes, adding timing, and other operations. |
Fault alarm | When an early warning and fault are generated, the device will push the alarm information to the cloud, and the push message can be received through the mobile app and web management platform. The alarm information contains the fault location and occurrence time. |
Profile | Multiple scenarios can be set to switch and switch multiple lines with one click (can be set across gateways). |
Data viewing | You can view the current voltage, current, power, temperature, leakage current, energy and other parameters of each line. |